DIN-1TSTAT8
Provides a DIN-rail mountable thermostat for multizone radiant heating systems. Works with Crestron remote temperature sensors and integrates with a Crestron® control system via Cresnet®. Provides relay control of eight heat zone valves and one main valve. Rated 1/2 HP at 240V AC.
Precio y disponibilidad para clientes
Con una cuenta ves tu precio en USD, el stock por depósito y podés armar tu pedido.
Dimensiones físicas
Ancho
16.1 cm
Alto
9.4 cm
Profundidad
6.0 cm
Peso
0.40 kg
Identificación del fabricante
Modelo
DIN-1TSTAT8
SKU fabricante
DIN-1TSTAT8
Especificaciones técnicas30
Documentación7
CAD Drawing for: DIN-1TSTAT8
Specifier Resources
Product Manual: DIN-1TSTAT8
Guides & Manuals
Product Information: DIN-1TSTAT8
Guides & Manuals
Spec Sheet for: DIN-1TSTAT8
Spec Sheets
Firmware : DIN-1TSTAT8 1.000.0039
Software & Firmware
Drawing for: DIN-1TSTAT8
Multimedia
Product Manual: DIN-1TSTAT8 (HTML)
Guides & Manuals
Descripción técnica
The DIN-1TSTAT8 is an 8-zone thermostat designed for use with radiant heating systems. Each zone requires a remote temperature sensor to be installed in each heating zone. Compatible sensors include models CHVI-RTS-1G-SM-W, CHVI-RTS-1G-N-W, CHV-RTS, and CHV-RSS. Each sensor connects to the DIN-1TSTAT8 via a single twisted pair wire. The DIN-1TSTAT8 installs at a central location in a DIN rail enclosure, and connects to a Crestron® control system via Cresnet®.[1]
Its connection to a control system allows each zone to be adjusted from a Crestron touch screen, handheld remote, mobile app, or computer. Customized automation and scheduling is also possible. The use of remote temperature sensors eliminates the need for a separate thermostat on the wall in each zone.
The DIN-1TSTAT8 is for heat-only applications using radiators or radiant floor heating. It controls the heating valve for each zone via eight SPDT relay control outputs (one per zone). A ninth main valve control output is also provided. Each relay includes normally open and normally closed contacts, and is rated for 1/2 HP at 240 Volts AC, 50/60 Hz.
The DIN-1TSTAT8 requires a Crestron control system to function. The heating setpoints for each zone are set by the user through the control system and then stored in memory on the DIN-1TSTAT8. In the event a user setpoint is lost, a failsafe operating mode takes over to keep the space heated at a preset temperature until the user setpoint is restored from the control system.[1]
Standard 35 mm DIN rail mounting allows the DIN-1TSTAT8 to be installed in a DIN rail enclosure (Crestron DIN-EN series or similar). It occupies 9 DIN module spaces, and is powered by the Cresnet control bus.
Key Features
• Eight-zone radiant heat control thermostat
• Works with Crestron® remote temperature sensors [1]
• Operates as part of a complete Crestron automation system [1]
• Failsafe mode ensures continuous heat if the user setpoint is temporarily lost
• Onboard controls and indicators for system testing
• Eight SPDT heat zone valve control relays
• One SPDT main valve control relay
• Rated 1/2 HP at 240 Volts AC, 50/60 Hz
• System integration via Cresnet®
• Cresnet powered (24 Volts DC)
• 9U 35 mm DIN rail mountable